Terminal Voltage during No Load Solution

STEP 0: Pre-Calculation Summary
Formula Used
No Load Terminal Voltage = (Primary Voltage*Number of Turns in Secondary)/Number of Turns in Primary
Vno-load = (V1*N2)/N1
This formula uses 4 Variables
Variables Used
No Load Terminal Voltage - (Measured in Volt) - No load terminal voltage is the no load voltage when zero current is drawn from the supply. The terminal voltage is equal to zero when there is no load in the electric circuit.
Primary Voltage - (Measured in Volt) - Primary Voltage means the level of voltage at facilities at which electric power is taken or delivered, generally at a level between 12 kV and 33 kV, but always between 2 kV and 50 kV.
Number of Turns in Secondary - The Number of Turns in Secondary Winding is the number of turns secondary winding is the winding of a transformer.
Number of Turns in Primary - The Number of Turns in Primary Winding is the number of turns primary winding is the winding of a transformer.
STEP 1: Convert Input(s) to Base Unit
Primary Voltage: 240 Volt --> 240 Volt No Conversion Required
Number of Turns in Secondary: 24 --> No Conversion Required
Number of Turns in Primary: 20 --> No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
Vno-load = (V1*N2)/N1 --> (240*24)/20
Evaluating ... ...
Vno-load = 288
STEP 3: Convert Result to Output's Unit
288 Volt --> No Conversion Required
FINAL ANSWER
288 Volt <-- No Load Terminal Voltage
(Calculation completed in 00.004 seconds)

Credits

Creator Image
Created by Satyajit Dan
Guru Nanak Institute Of Technology (GNIT), Kolkata
Satyajit Dan has created this Calculator and 5 more calculators!
Verifier Image
Verified by swetha samavedam
Delhi Technological University (DTU), delhi
swetha samavedam has verified this Calculator and 10 more calculators!

Voltage and EMF Calculators

Output Voltage given EMF Induced in Secondary Winding
​ LaTeX ​ Go Secondary Voltage = EMF Induced in Secondary-Secondary Current*Impedance of Secondary
Input Voltage when EMF Induced in Primary Winding
​ LaTeX ​ Go Primary Voltage = EMF Induced in Primary+Primary Current*Impedance of Primary
EMF Induced in Secondary Winding given Voltage Transformation Ratio
​ LaTeX ​ Go EMF Induced in Secondary = EMF Induced in Primary*Transformation Ratio
EMF Induced in Primary Winding given Voltage Transformation Ratio
​ LaTeX ​ Go EMF Induced in Primary = EMF Induced in Secondary/Transformation Ratio

Transformer Circuit Calculators

Equivalent Reactance of Transformer from Secondary Side
​ LaTeX ​ Go Equivalent Reactance from Secondary = Secondary Leakage Reactance+Reactance of Primary in Secondary
Equivalent Reactance of Transformer from Primary Side
​ LaTeX ​ Go Equivalent Reactance from Primary = Primary Leakage Reactance+Reactance of Secondary in Primary
Primary Leakage Reactance
​ LaTeX ​ Go Primary Leakage Reactance = Reactance of Primary in Secondary/(Transformation Ratio^2)
Reactance of Primary Winding in Secondary
​ LaTeX ​ Go Reactance of Primary in Secondary = Primary Leakage Reactance*Transformation Ratio^2

Terminal Voltage during No Load Formula

​LaTeX ​Go
No Load Terminal Voltage = (Primary Voltage*Number of Turns in Secondary)/Number of Turns in Primary
Vno-load = (V1*N2)/N1

What is winding in Transformer ?

Transformers have two windings, the primary winding and the secondary winding. The primary winding is the coil that draws power from the source. The secondary winding is the coil that delivers the energy at the transformed or changed voltage to the load.

How to Calculate Terminal Voltage during No Load?

Terminal Voltage during No Load calculator uses No Load Terminal Voltage = (Primary Voltage*Number of Turns in Secondary)/Number of Turns in Primary to calculate the No Load Terminal Voltage, Terminal Voltage during No Load means the secondary winding is open-circuited, which means there is no load on the secondary side of the transformer and, therefore, current in the secondary will be zero. No Load Terminal Voltage is denoted by Vno-load symbol.

How to calculate Terminal Voltage during No Load using this online calculator? To use this online calculator for Terminal Voltage during No Load, enter Primary Voltage (V1), Number of Turns in Secondary (N2) & Number of Turns in Primary (N1) and hit the calculate button. Here is how the Terminal Voltage during No Load calculation can be explained with given input values -> 288 = (240*24)/20.

FAQ

What is Terminal Voltage during No Load?
Terminal Voltage during No Load means the secondary winding is open-circuited, which means there is no load on the secondary side of the transformer and, therefore, current in the secondary will be zero and is represented as Vno-load = (V1*N2)/N1 or No Load Terminal Voltage = (Primary Voltage*Number of Turns in Secondary)/Number of Turns in Primary. Primary Voltage means the level of voltage at facilities at which electric power is taken or delivered, generally at a level between 12 kV and 33 kV, but always between 2 kV and 50 kV, The Number of Turns in Secondary Winding is the number of turns secondary winding is the winding of a transformer & The Number of Turns in Primary Winding is the number of turns primary winding is the winding of a transformer.
How to calculate Terminal Voltage during No Load?
Terminal Voltage during No Load means the secondary winding is open-circuited, which means there is no load on the secondary side of the transformer and, therefore, current in the secondary will be zero is calculated using No Load Terminal Voltage = (Primary Voltage*Number of Turns in Secondary)/Number of Turns in Primary. To calculate Terminal Voltage during No Load, you need Primary Voltage (V1), Number of Turns in Secondary (N2) & Number of Turns in Primary (N1). With our tool, you need to enter the respective value for Primary Voltage, Number of Turns in Secondary & Number of Turns in Primary and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!