How to Calculate Resonance Frequency for Shunt Capacitor Compensation?
Resonance Frequency for Shunt Capacitor Compensation calculator uses Resonance Frequency of Shunt Capacitor = Operating System Frequency*sqrt(1/(1-Degree in Shunt Compensation)) to calculate the Resonance Frequency of Shunt Capacitor, The Resonance Frequency for Shunt Capacitor Compensation formula is defined as the resonance at which excessive current and voltage levels, increases leading to equipment damage and potential system instability. Resonance Frequency of Shunt Capacitor is denoted by fr(sh) symbol.
How to calculate Resonance Frequency for Shunt Capacitor Compensation using this online calculator? To use this online calculator for Resonance Frequency for Shunt Capacitor Compensation, enter Operating System Frequency (fop) & Degree in Shunt Compensation (ksh) and hit the calculate button. Here is how the Resonance Frequency for Shunt Capacitor Compensation calculation can be explained with given input values -> 84.85281 = 60*sqrt(1/(1-0.5)).