How to Calculate Pressure Drop in Plate Type Heat Exchanger given Reynolds Number?
Pressure Drop in Plate Type Heat Exchanger given Reynolds Number calculator uses Plate Pressure Drop = 8*(0.6*(Reynold Number^(-0.3)))*(Path Length/Equivalent Diameter)*(Fluid Density*(Channel Velocity^2)/2) to calculate the Plate Pressure Drop, The Pressure Drop in Plate Type Heat Exchanger given Reynolds Number formula is defined as the decrease in pressure experienced by the fluid as it travels through the flow channels created by the stacked plates. Plate Pressure Drop is denoted by ΔPp symbol.
How to calculate Pressure Drop in Plate Type Heat Exchanger given Reynolds Number using this online calculator? To use this online calculator for Pressure Drop in Plate Type Heat Exchanger given Reynolds Number, enter Reynold Number (Re), Path Length (Lp), Equivalent Diameter (De), Fluid Density (ρfluid) & Channel Velocity (up) and hit the calculate button. Here is how the Pressure Drop in Plate Type Heat Exchanger given Reynolds Number calculation can be explained with given input values -> 120988.3 = 8*(0.6*(23.159^(-0.3)))*(0.63147/0.016528)*(995*(1.845^2)/2).