How to Calculate Pressure Drop in Plate Type Heat Exchanger?
Pressure Drop in Plate Type Heat Exchanger calculator uses Plate Pressure Drop = 8*Friction Factor*(Path Length/Equivalent Diameter)*(Fluid Density*(Channel Velocity^2))/2 to calculate the Plate Pressure Drop, The Pressure Drop in Plate Type Heat Exchanger formula refers to the loss of fluid pressure as the fluid flows through the channels formed by the plates. Plate pressure drop is the decrease in pressure experienced by the fluid as it travels through the flow channels created by the stacked plates. Plate Pressure Drop is denoted by ΔPp symbol.
How to calculate Pressure Drop in Plate Type Heat Exchanger using this online calculator? To use this online calculator for Pressure Drop in Plate Type Heat Exchanger, enter Friction Factor (Jf), Path Length (Lp), Equivalent Diameter (De), Fluid Density (ρfluid) & Channel Velocity (up) and hit the calculate button. Here is how the Pressure Drop in Plate Type Heat Exchanger calculation can be explained with given input values -> 2070.467 = 8*0.004*(0.63147/0.016528)*(995*(1.845^2))/2.