How to Calculate Length using Area of X-Section (2 Phase 4 Wire US)?
Length using Area of X-Section (2 Phase 4 Wire US) calculator uses Length of Underground AC Wire = (Area of Underground AC Wire*Line Losses*(Maximum Voltage Underground AC^2)*(cos(Phase Difference))^2)/(4*Resistivity*(Power Transmitted^2)) to calculate the Length of Underground AC Wire, The Length using Area of X-Section (2 phase 4 wire US) formula is defined as the total length of the wire that used in the two-phase four-wire system. Length of Underground AC Wire is denoted by L symbol.
How to calculate Length using Area of X-Section (2 Phase 4 Wire US) using this online calculator? To use this online calculator for Length using Area of X-Section (2 Phase 4 Wire US), enter Area of Underground AC Wire (A), Line Losses (Ploss), Maximum Voltage Underground AC (Vm), Phase Difference (Φ), Resistivity (ρ) & Power Transmitted (P) and hit the calculate button. Here is how the Length using Area of X-Section (2 Phase 4 Wire US) calculation can be explained with given input values -> 22155.76 = (1.28*2.67*(230^2)*(cos(0.5235987755982))^2)/(4*1.7E-05*(300^2)).