Heat Transfer Coefficient for Condensation Outside Vertical Tubes Solution

STEP 0: Pre-Calculation Summary
Formula Used
Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3)
haverage = 0.926*kf*((ρf/μ)*(ρf-ρV)*[g]*(pi*DO*Nt/Mf))^(1/3)
This formula uses 2 Constants, 8 Variables
Constants Used
[g] - Gravitational acceleration on Earth Value Taken As 9.80665
pi - Archimedes' constant Value Taken As 3.14159265358979323846264338327950288
Variables Used
Average Condensation Coefficient - (Measured in Watt per Square Meter per Kelvin) - Average Condensation Coefficient is the mean heat transfer coefficient considering both inner and outer heat transfer during condensation.
Thermal Conductivity in Heat Exchanger - (Measured in Watt per Meter per K) - Thermal Conductivity in Heat Exchanger is the proportionality constant for the heat flux during conduction heat transfer in a heat exchanger.
Fluid Density in Heat Transfer - (Measured in Kilogram per Cubic Meter) - Fluid Density in Heat Transfer is defined as the ratio of mass of given fluid with respect to the volume that it occupies.
Fluid Viscosity at Average Temperature - (Measured in Pascal Second) - Fluid viscosity at Average Temperature in Heat Exchanger is a fundamental property of fluids that characterizes their resistance to flow in a heat exchanger.
Density of Vapor - (Measured in Kilogram per Cubic Meter) - Density of Vapor is defined as the ratio of mass to the volume of vapor at particular temperature.
Pipe Outer Dia - (Measured in Meter) - Pipe Outer Dia refers to the measurement of the outside or external diameter of a cylindrical pipe. It includes the pipe thickness into it.
Number of Tubes in Heat Exchanger - Number of Tubes in Heat Exchanger refers to the count of individual tubes that form the heat transfer surface inside the heat exchanger.
Mass Flowrate in Heat Exchanger - (Measured in Kilogram per Second) - Mass Flowrate in Heat Exchanger is the mass of a substance that passes per unit of time in a Heat Exchanger.
STEP 1: Convert Input(s) to Base Unit
Thermal Conductivity in Heat Exchanger: 3.4 Watt per Meter per K --> 3.4 Watt per Meter per K No Conversion Required
Fluid Density in Heat Transfer: 995 Kilogram per Cubic Meter --> 995 Kilogram per Cubic Meter No Conversion Required
Fluid Viscosity at Average Temperature: 1.005 Pascal Second --> 1.005 Pascal Second No Conversion Required
Density of Vapor: 1.712 Kilogram per Cubic Meter --> 1.712 Kilogram per Cubic Meter No Conversion Required
Pipe Outer Dia: 19 Millimeter --> 0.019 Meter (Check conversion ​here)
Number of Tubes in Heat Exchanger: 360 --> No Conversion Required
Mass Flowrate in Heat Exchanger: 14 Kilogram per Second --> 14 Kilogram per Second No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
haverage = 0.926*kf*((ρf/μ)*(ρfV)*[g]*(pi*DO*Nt/Mf))^(1/3) --> 0.926*3.4*((995/1.005)*(995-1.712)*[g]*(pi*0.019*360/14))^(1/3)
Evaluating ... ...
haverage = 773.036815980312
STEP 3: Convert Result to Output's Unit
773.036815980312 Watt per Square Meter per Kelvin --> No Conversion Required
FINAL ANSWER
773.036815980312 773.0368 Watt per Square Meter per Kelvin <-- Average Condensation Coefficient
(Calculation completed in 00.004 seconds)

Credits

Creator Image
Created by Rishi Vadodaria
Malviya National Institute Of Technology (MNIT JAIPUR ), JAIPUR
Rishi Vadodaria has created this Calculator and 200+ more calculators!
Verifier Image
Verified by Heet
Thadomal Shahani Engineering College (Tsec), Mumbai
Heet has verified this Calculator and 25+ more calculators!

Heat Transfer Coefficient in Heat Exchangers Calculators

Heat Transfer Coefficient for Condensation Outside Horizontal Tubes
​ LaTeX ​ Go Average Condensation Coefficient = 0.95*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer*(Fluid Density in Heat Transfer-Density of Vapor)*([g]/Fluid Viscosity at Average Temperature)*(Number of Tubes in Heat Exchanger*Length of Tube in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3))*(Number of Tubes in Vertical Row of Exchanger^(-1/6))
Heat Transfer Coefficient for Condensation Inside Vertical Tubes
​ LaTeX ​ Go Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Inner Diameter in Exchanger*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3)
Heat Transfer Coefficient for Condensation Outside Vertical Tubes
​ LaTeX ​ Go Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3)
Heat Transfer Coefficient for Plate Heat Exchanger
​ LaTeX ​ Go Plate Film Coefficient = 0.26*(Thermal Conductivity in Heat Exchanger/Equivalent Diameter in Heat Exchanger)*(Reynold Number for Fluid^0.65)*(Prandlt Number for Fluid^0.4)*(Fluid Viscosity at Average Temperature/Fluid Viscosity at Tube Wall Temperature)^0.14

Heat Transfer Coefficient for Condensation Outside Vertical Tubes Formula

​LaTeX ​Go
Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3)
haverage = 0.926*kf*((ρf/μ)*(ρf-ρV)*[g]*(pi*DO*Nt/Mf))^(1/3)

What is Condenser?

Condenser is a special type of Heat Exchanger in which hot vapors transfer their latent heat to the colder fluid and thus results into condensation of vapors into liquid phase.

What is Heat Transfer Coefficient for Condensation Outside Tubes?

Heat Transfer Coefficient for Condensation Outside Tubes is the heat transfer coefficient when the vapors gets condensed into liquid phase on to the surface of tubes in a shell and tube heat exchanger. The Condenser orientation in such process is vertical positioning and the vapors are allowed to condense over the external surface of the tubes present.

How to Calculate Heat Transfer Coefficient for Condensation Outside Vertical Tubes?

Heat Transfer Coefficient for Condensation Outside Vertical Tubes calculator uses Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3) to calculate the Average Condensation Coefficient, The Heat Transfer Coefficient for Condensation Outside Vertical Tubes formula is defined as the film coefficient for heat transfer when the vapors are condensed outside a vertical tube into its liquid phase. Average Condensation Coefficient is denoted by haverage symbol.

How to calculate Heat Transfer Coefficient for Condensation Outside Vertical Tubes using this online calculator? To use this online calculator for Heat Transfer Coefficient for Condensation Outside Vertical Tubes, enter Thermal Conductivity in Heat Exchanger (kf), Fluid Density in Heat Transfer f), Fluid Viscosity at Average Temperature (μ), Density of Vapor V), Pipe Outer Dia (DO), Number of Tubes in Heat Exchanger (Nt) & Mass Flowrate in Heat Exchanger (Mf) and hit the calculate button. Here is how the Heat Transfer Coefficient for Condensation Outside Vertical Tubes calculation can be explained with given input values -> 773.0373 = 0.926*3.4*((995/1.005)*(995-1.712)*[g]*(pi*0.019*360/14))^(1/3).

FAQ

What is Heat Transfer Coefficient for Condensation Outside Vertical Tubes?
The Heat Transfer Coefficient for Condensation Outside Vertical Tubes formula is defined as the film coefficient for heat transfer when the vapors are condensed outside a vertical tube into its liquid phase and is represented as haverage = 0.926*kf*((ρf/μ)*(ρfV)*[g]*(pi*DO*Nt/Mf))^(1/3) or Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3). Thermal Conductivity in Heat Exchanger is the proportionality constant for the heat flux during conduction heat transfer in a heat exchanger, Fluid Density in Heat Transfer is defined as the ratio of mass of given fluid with respect to the volume that it occupies, Fluid viscosity at Average Temperature in Heat Exchanger is a fundamental property of fluids that characterizes their resistance to flow in a heat exchanger, Density of Vapor is defined as the ratio of mass to the volume of vapor at particular temperature, Pipe Outer Dia refers to the measurement of the outside or external diameter of a cylindrical pipe. It includes the pipe thickness into it, Number of Tubes in Heat Exchanger refers to the count of individual tubes that form the heat transfer surface inside the heat exchanger & Mass Flowrate in Heat Exchanger is the mass of a substance that passes per unit of time in a Heat Exchanger.
How to calculate Heat Transfer Coefficient for Condensation Outside Vertical Tubes?
The Heat Transfer Coefficient for Condensation Outside Vertical Tubes formula is defined as the film coefficient for heat transfer when the vapors are condensed outside a vertical tube into its liquid phase is calculated using Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Outer Dia*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3). To calculate Heat Transfer Coefficient for Condensation Outside Vertical Tubes, you need Thermal Conductivity in Heat Exchanger (kf), Fluid Density in Heat Transfer f), Fluid Viscosity at Average Temperature (μ), Density of Vapor V), Pipe Outer Dia (DO), Number of Tubes in Heat Exchanger (Nt) & Mass Flowrate in Heat Exchanger (Mf). With our tool, you need to enter the respective value for Thermal Conductivity in Heat Exchanger, Fluid Density in Heat Transfer, Fluid Viscosity at Average Temperature, Density of Vapor, Pipe Outer Dia, Number of Tubes in Heat Exchanger & Mass Flowrate in Heat Exchanger and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Average Condensation Coefficient?
In this formula, Average Condensation Coefficient uses Thermal Conductivity in Heat Exchanger, Fluid Density in Heat Transfer, Fluid Viscosity at Average Temperature, Density of Vapor, Pipe Outer Dia, Number of Tubes in Heat Exchanger & Mass Flowrate in Heat Exchanger. We can use 3 other way(s) to calculate the same, which is/are as follows -
  • Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer/Fluid Viscosity at Average Temperature)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]*(pi*Pipe Inner Diameter in Exchanger*Number of Tubes in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3)
  • Average Condensation Coefficient = 0.95*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer*(Fluid Density in Heat Transfer-Density of Vapor)*([g]/Fluid Viscosity at Average Temperature)*(Number of Tubes in Heat Exchanger*Length of Tube in Heat Exchanger/Mass Flowrate in Heat Exchanger))^(1/3))*(Number of Tubes in Vertical Row of Exchanger^(-1/6))
  • Average Condensation Coefficient = 0.926*Thermal Conductivity in Heat Exchanger*((Fluid Density in Heat Transfer)*(Fluid Density in Heat Transfer-Density of Vapor)*[g]/((Fluid Viscosity at Average Temperature*Tube Loading)))^(1/3)
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!