Formula Used
Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263)
DBundle = DiaO*(NT/0.158)^(1/2.263)
This formula uses 3 Variables
Variables Used
Bundle Diameter - (Measured in Meter) - Bundle Diameter refers to the diameter of the tube bundle within the heat exchanger.
Pipe Outer Diameter in Bundle Diameter - (Measured in Meter) - Pipe Outer Diameter in Bundle Diameter refers to the measurement of the outside or external diameter of a cylindrical pipe. It includes the pipe thickness into it.
Number of Tubes in Bundle Diameter - Number of Tubes in Bundle Diameter in a heat exchanger refers to the count of individual tubes that form the heat transfer surface inside the heat exchanger forming a bundle of tubes.
STEP 1: Convert Input(s) to Base Unit
Pipe Outer Diameter in Bundle Diameter: 19.2 Millimeter --> 0.0192 Meter (Check conversion ​here)
Number of Tubes in Bundle Diameter: 325 --> No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
DBundle = DiaO*(NT/0.158)^(1/2.263) --> 0.0192*(325/0.158)^(1/2.263)
Evaluating ... ...
DBundle = 0.558968168286568
STEP 3: Convert Result to Output's Unit
0.558968168286568 Meter -->558.968168286568 Millimeter (Check conversion ​here)
FINAL ANSWER
558.968168286568 558.9682 Millimeter <-- Bundle Diameter
(Calculation completed in 00.004 seconds)

Credits

Creator Image
Created by Rishi Vadodaria
Malviya National Institute Of Technology (MNIT JAIPUR ), JAIPUR
Rishi Vadodaria has created this Calculator and 200+ more calculators!
Verifier Image
Verified by Vaibhav Mishra
DJ Sanghvi College of Engineering (DJSCE), Mumbai
Vaibhav Mishra has verified this Calculator and 200+ more calculators!

Bundle Diameter in Heat Exchanger Calculators

Bundle Diameter for Eight Tube Pass Triangular Pitch in Heat Exchanger
​ LaTeX ​ Go Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.0365)^(1/2.675)
Bundle Diameter for Eight Tube Pass Square Pitch in Heat Exchanger
​ LaTeX ​ Go Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.0331)^(1/2.643)
Bundle Diameter for Four Tube Pass Triangular Pitch in Heat Exchanger
​ LaTeX ​ Go Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.175)^(1/2.285)
Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger
​ LaTeX ​ Go Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263)

Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger Formula

​LaTeX ​Go
Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263)
DBundle = DiaO*(NT/0.158)^(1/2.263)

What is Shell and Tube heat exchanger?

A Shell and Tube Heat Exchanger is a common type of heat exchanger used in various industrial applications to transfer heat between two fluids. It consists of a large, cylindrical outer shell (usually made of metal) with multiple smaller tubes (also made of metal) running through it. The tubes are arranged in a bundle inside the shell and are typically oriented parallel to the shell's longitudinal axis.

What is Bundle Diameter in Heat Exchanger?

The bundle diameter in a shell and tube heat exchanger is the diameter of the tube bundle, which is a critical component influencing heat transfer efficiency, pressure drop, and maintenance considerations.

In a shell and tube heat exchanger, a "Four-tube pass" arrangement refers to a specific configuration in which one of the fluids passes through the tubes four times before exiting the heat exchanger.

How to Calculate Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger?

Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger calculator uses Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263) to calculate the Bundle Diameter, The Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger formula is defined as diameter of the tube bundle with Four or Multiple tube-pass within the heat exchanger having Square pitch layout with pitch equal to 1.25 times the outer diameter on tube-side. Bundle Diameter is denoted by DBundle symbol.

How to calculate Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger using this online calculator? To use this online calculator for Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger, enter Pipe Outer Diameter in Bundle Diameter (DiaO) & Number of Tubes in Bundle Diameter (NT) and hit the calculate button. Here is how the Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger calculation can be explained with given input values -> 558968.2 = 0.0192*(325/0.158)^(1/2.263).

FAQ

What is Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger?
The Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger formula is defined as diameter of the tube bundle with Four or Multiple tube-pass within the heat exchanger having Square pitch layout with pitch equal to 1.25 times the outer diameter on tube-side and is represented as DBundle = DiaO*(NT/0.158)^(1/2.263) or Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263). Pipe Outer Diameter in Bundle Diameter refers to the measurement of the outside or external diameter of a cylindrical pipe. It includes the pipe thickness into it & Number of Tubes in Bundle Diameter in a heat exchanger refers to the count of individual tubes that form the heat transfer surface inside the heat exchanger forming a bundle of tubes.
How to calculate Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger?
The Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger formula is defined as diameter of the tube bundle with Four or Multiple tube-pass within the heat exchanger having Square pitch layout with pitch equal to 1.25 times the outer diameter on tube-side is calculated using Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.158)^(1/2.263). To calculate Bundle Diameter for Four Tube Pass Square Pitch in Heat Exchanger, you need Pipe Outer Diameter in Bundle Diameter (DiaO) & Number of Tubes in Bundle Diameter (NT). With our tool, you need to enter the respective value for Pipe Outer Diameter in Bundle Diameter & Number of Tubes in Bundle Diameter and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate Bundle Diameter?
In this formula, Bundle Diameter uses Pipe Outer Diameter in Bundle Diameter & Number of Tubes in Bundle Diameter. We can use 3 other way(s) to calculate the same, which is/are as follows -
  • Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.0331)^(1/2.643)
  • Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.0365)^(1/2.675)
  • Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.175)^(1/2.285)
Let Others Know
Facebook
Twitter
Reddit
LinkedIn
Email
WhatsApp
Copied!