How to Calculate A-Phase EMF using Positive Sequence Current (Two Conductor Open)?
A-Phase EMF using Positive Sequence Current (Two Conductor Open) calculator uses A Phase EMF in TCO = Positive Sequence Current in TCO*(Positive Sequence Impedance in TCO+Negative Sequence Impedance in TCO+Zero Sequence Impedance in TCO) to calculate the A Phase EMF in TCO, A-Phase EMF using Positive Sequence Current (Two conductor open) formula is defined as the electromotive force that is induced into the two open conductor fault system. A Phase EMF in TCO is denoted by Ea(tco) symbol.
How to calculate A-Phase EMF using Positive Sequence Current (Two Conductor Open) using this online calculator? To use this online calculator for A-Phase EMF using Positive Sequence Current (Two Conductor Open), enter Positive Sequence Current in TCO (I1(tco)), Positive Sequence Impedance in TCO (Z1(tco)), Negative Sequence Impedance in TCO (Z2(tco)) & Zero Sequence Impedance in TCO (Z0(tco)) and hit the calculate button. Here is how the A-Phase EMF using Positive Sequence Current (Two Conductor Open) calculation can be explained with given input values -> 121.404 = 2.01*(7.95+44.5+7.96).