A-Phase EMF using Positive Sequence Voltage(LLF) Solution

STEP 0: Pre-Calculation Summary
Formula Used
A Phase EMF = (Positive Sequence Voltage*(Positive Sequence Impedance+Negative Sequence Impedance))/Negative Sequence Impedance
Ea = (V1*(Z1+Z2))/Z2
This formula uses 4 Variables
Variables Used
A Phase EMF - (Measured in Volt) - A phase EMF is defined as the electromagnetic force of the a-phase in open conductor fault.
Positive Sequence Voltage - (Measured in Volt) - Positive Sequence Voltage consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
Positive Sequence Impedance - (Measured in Ohm) - Positive Sequence Impedance consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
Negative Sequence Impedance - (Measured in Ohm) - Negative Sequence Impedance consists of balanced three-phase impedance phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
STEP 1: Convert Input(s) to Base Unit
Positive Sequence Voltage: 17.5 Volt --> 17.5 Volt No Conversion Required
Positive Sequence Impedance: 7.94 Ohm --> 7.94 Ohm No Conversion Required
Negative Sequence Impedance: -44.6 Ohm --> -44.6 Ohm No Conversion Required
STEP 2: Evaluate Formula
Substituting Input Values in Formula
Ea = (V1*(Z1+Z2))/Z2 --> (17.5*(7.94+(-44.6)))/(-44.6)
Evaluating ... ...
Ea = 14.3845291479821
STEP 3: Convert Result to Output's Unit
14.3845291479821 Volt --> No Conversion Required
FINAL ANSWER
14.3845291479821 14.38453 Volt <-- A Phase EMF
(Calculation completed in 00.008 seconds)

Credits

Creator Image
Created by Nisarg
Indian Institute of Technology,Roorlee (IITR), Roorkee
Nisarg has created this Calculator and 100+ more calculators!
Verifier Image
Verified by Parminder Singh
Chandigarh University (CU), Punjab
Parminder Singh has verified this Calculator and 500+ more calculators!

Voltage and EMF Calculators

C-Phase Voltage using C-Phase Current (LLF)
​ LaTeX ​ Go C Phase Voltage = B Phase Voltage+(Fault Impedance*C Phase Current)
B-Phase Voltage using C-Phase Current (LLF)
​ LaTeX ​ Go B Phase Voltage = C Phase Voltage-(Fault Impedance*C Phase Current)
B-Phase Voltage (LLF)
​ LaTeX ​ Go B Phase Voltage = (Fault Impedance*B Phase Current)+C Phase Voltage
C-Phase Voltage (LLF)
​ LaTeX ​ Go C Phase Voltage = B Phase Voltage-(Fault Impedance*B Phase Current)

A-Phase EMF using Positive Sequence Voltage(LLF) Formula

​LaTeX ​Go
A Phase EMF = (Positive Sequence Voltage*(Positive Sequence Impedance+Negative Sequence Impedance))/Negative Sequence Impedance
Ea = (V1*(Z1+Z2))/Z2

What is a line to line fault?

A line-to-line fault, also known as a three-phase fault, is a type of electrical fault that occurs in a three-phase power system. This type of fault occurs when a failure occurs between two phases of the power system, causing a current to flow from one phase to the other.

How to Calculate A-Phase EMF using Positive Sequence Voltage(LLF)?

A-Phase EMF using Positive Sequence Voltage(LLF) calculator uses A Phase EMF = (Positive Sequence Voltage*(Positive Sequence Impedance+Negative Sequence Impedance))/Negative Sequence Impedance to calculate the A Phase EMF, The A-phase EMF using Positive Sequence Voltage(LLF) formula is defined as the electrical potential difference that is present in one phase of a three-phase electrical power system during a fault condition. A Phase EMF is denoted by Ea symbol.

How to calculate A-Phase EMF using Positive Sequence Voltage(LLF) using this online calculator? To use this online calculator for A-Phase EMF using Positive Sequence Voltage(LLF), enter Positive Sequence Voltage (V1), Positive Sequence Impedance (Z1) & Negative Sequence Impedance (Z2) and hit the calculate button. Here is how the A-Phase EMF using Positive Sequence Voltage(LLF) calculation can be explained with given input values -> 11.09664 = (17.5*(7.94+(-44.6)))/(-44.6).

FAQ

What is A-Phase EMF using Positive Sequence Voltage(LLF)?
The A-phase EMF using Positive Sequence Voltage(LLF) formula is defined as the electrical potential difference that is present in one phase of a three-phase electrical power system during a fault condition and is represented as Ea = (V1*(Z1+Z2))/Z2 or A Phase EMF = (Positive Sequence Voltage*(Positive Sequence Impedance+Negative Sequence Impedance))/Negative Sequence Impedance. Positive Sequence Voltage consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation, Positive Sequence Impedance consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation & Negative Sequence Impedance consists of balanced three-phase impedance phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
How to calculate A-Phase EMF using Positive Sequence Voltage(LLF)?
The A-phase EMF using Positive Sequence Voltage(LLF) formula is defined as the electrical potential difference that is present in one phase of a three-phase electrical power system during a fault condition is calculated using A Phase EMF = (Positive Sequence Voltage*(Positive Sequence Impedance+Negative Sequence Impedance))/Negative Sequence Impedance. To calculate A-Phase EMF using Positive Sequence Voltage(LLF), you need Positive Sequence Voltage (V1), Positive Sequence Impedance (Z1) & Negative Sequence Impedance (Z2). With our tool, you need to enter the respective value for Positive Sequence Voltage, Positive Sequence Impedance & Negative Sequence Impedance and hit the calculate button. You can also select the units (if any) for Input(s) and the Output as well.
How many ways are there to calculate A Phase EMF?
In this formula, A Phase EMF uses Positive Sequence Voltage, Positive Sequence Impedance & Negative Sequence Impedance. We can use 3 other way(s) to calculate the same, which is/are as follows -
  • A Phase EMF = Positive Sequence Voltage+Positive Sequence Impedance*Positive Sequence Current
  • A Phase EMF = Positive Sequence Current*(Positive Sequence Impedance+Negative Sequence Impedance+Fault Impedance)
  • A Phase EMF = (Fault Current*(Positive Sequence Impedance+Negative Sequence Impedance))/sqrt(3)